CVSS 9.4 for a password reset that requires nothing more than an HTTP GET request. That's the ugly reality of CVE-2026-0647, a missing-authentication vulnerability in Rockwell Automation's 1794-AENTR and 1794-AENTRXT FLEX I/O EtherNet/IP adapters.
The Flaw That Shouldn't Exist
Rockwell's own advisory admits the embedded web server allows an unauthenticated attacker to change the device's password by sending a crafted HTTP GET to a specific endpoint. No prior login, no session token, no challenge. Just a well-formed request and the attacker owns the web interface. That leads to unauthorized access, account takeover, and effectively a bricked web server for the legitimate operator.
CVE-2026-0646 pairs with it: a denial-of-service bug caused by improper memory handling of CIP protocol requests. A single malformed packet can fault the adapter, dropping the connection to all attached I/O modules. Recovery requires a manual reset on the factory floor. CVSS 7.5, but in a production line every minute of downtime costs real money.
Affected Gear and the Fix
Both vulnerabilities hit the 1794-AENTR and 1794-AENTRXT running firmware version V2.012. Rockwell shipped the fix in version 2.013, detailed in security advisory SD1775. CISA's advisory notes that these devices are deployed worldwide across critical manufacturing sectors. If you have these in a control network, you should treat them as compromised until patched.
No exploitation in the wild reported yet, but the attack surface is trivial. An unauthenticated HTTP GET to change a password is not something that requires nation-state resources; any script kiddie with a Shodan scan could pull it off.
What You Should Do
Update to 2.013 immediately. Also isolate these adapters from any network that touches the internet or untrusted zones. Rockwell's recommended practices line up with CISA's: firewalls, VPNs, and defense-in-depth. But the biggest single action is the firmware update - that closes both doors at once.
This pair of vulnerabilities is a reminder that industrial gear's web interfaces are often an afterthought, and that afterthought can hand an attacker the keys to the plant floor.
Source: Rockwell Automation FLEX I/O EtherNet/IP Adapters